Loading...

Delta Electronics DIAEnergie

View CSAF

1. EXECUTIVE SUMMARY

CVSS v4 9.3
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Delta Electronics
Equipment: DIAEnergie
Vulnerabilities: SQL Injection

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to retrieve records or cause a denial of service.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Delta Electronics DIAEnergie, an industrial energy management system, are affected:

DIAEnergie: Versions v1.10.01.008 and prior.

3.2 Vulnerability Overview

3.2.1 SQL Injection CWE-89

Delta Electronics DIAEnergie is vulnerable to an SQL injection in the script AM_RegReport.aspx. An unauthenticated attacker may be able to exploit this issue to obtain records contained in the targeted product.

CVE-2024-43699 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-43699. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 SQL Injection CWE-89

Delta Electronics DIAEnergie is vulnerable to an SQL injection in the script Handler_CFG.ashx. An authenticated attacker may be able to exploit this issue to cause delay in the targeted product.

CVE-2024-42417 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-42417. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Michael Heinzl reported these vulnerabilities to CISA.

4. MITIGATIONS

Delta recommends users update to DIAEnergie v1.10.01.009. Users can request this version of DIAEnergie from Delta Electronics’ regional sales or agents.

For more information on this issue, please see the Delta product cybersecurity advisory.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

October 3, 2024: Initial Publication

Leave a Reply

Your email address will not be published. Required fields are marked *